    LHJCZR2-7.2DJY/D315-40TM(D)
    LHJCZR2-12DJY/D200-40TM(D)

    Removable type AC high voltage vacuum contactor—fuse composite apparatus
    It is rated 7.2kV/315A、12kV/200A, phase spacing is 150mm, and pole spacing is 275mm. It can use mechanical holding type or electric holding type. The product is installed in the 800mm wide switchboard.

    Name

    Unit

    Value

    Main circuit

    Rated working voltage (Ue)

    kV

    7.2

    12

    Rated working current (Ie) (due to fuse)

    A

    ≤315

    ≤200

    Rated frequency (fr)

    Hz

    50~60

    Rated making capacity

    A

    10Ie

    Rated breaking capacity

    A

    8Ie

    Rated short time withstand current

    kA

    6.3

    Rated peak withstand current

    kA

    40

    Rated short circuit duration

    s

    4

    Rated anticipated short circuit breaking current (due to fuse)

    kA

    ≤40

    Rated anticipated short circuit making current

    kA

    100

    Take-over current

    A

    3150

    Power frequency withstand voltage

    Between phases, phase to earth

    kV

    32

    42

    Vacuum breaks

    kV

    32

    42

    Lightening impulse withstand voltage

    kV

    60

    75

    Control circuit

    Rated voltage1 (Us)

    V

    AC or DC. 110/220

    Rated power (Ps)

    Electric holding

    VA

    ≤1000/100 (absorbing/holding)

    Mechanical holding

    VA

    ≤900/350 (closing/opening)

    Auxiliary circuit

    Form

     

    6a+6b

    Rated value

     

    AC200V/5A

    Control circuit, auxiliary circuit to earth power frequency withstand voltage

    kV

    2

    Rated operating frequency

    Long-term or mechanical holding type

    time/h

    300

    Short-term

    time/h

    600

    Mechanical endurance

    10000 times

    30

    Electrical endurance

    10000 times

    10(AC-3)

    Mechanical characteristics

    Closing time

    ms

    ≤150

    Original opening time

    ms

    ≤150(electric holding)

    ≤60(mechanical holding)

    3-phase synchronism

    ms

    ≤3

    Closing tripping

    ms

    ≤6

    Remark: 1.rated control voltage can be made according to customer’s requirements.

     
     
     